CompactLogix, ControlLogix & Micro PLC Sizing Calculator
Short answer: The right Allen-Bradley PLC is the smallest controller that satisfies every requirement plus a design reserve — memory, EtherNet/IP nodes, local and remote I/O, motion, safety, communications, and performance — not just the smallest one with enough memory.
Estimate the right Micro800, CompactLogix, or ControlLogix processor based on your actual machine — including Machine Builder Library objects, networking, motion, safety, and future capacity. CompactLogix 5390 and ControlLogix 5590 (L9) are evaluated alongside 5380 and 5580.
Automation Ready Panels specializes in configurable Allen-Bradley control panels. Qualifying standard configurations are quoted, designed, programmed, and shipped in 7–10 business days. Send what you have and we’ll respond within 30 minutes.
Interactive calculator
Size my Allen-Bradley PLC
Pick a starting point. Blank counts are treated as zero. The tool checks every ARP-supported controller from smallest to largest against memory, EtherNet/IP nodes, local I/O, remote I/O, motion, safety, performance, and architecture, and stops at the smallest one that passes all of them. No contact information is requested.
Interpreted in your browser only; nothing is sent. Nothing is calculated until you confirm the quantities.
Loaded into the questionnaire below. Check the remaining questions, then press Calculate.
Build My Application — questionnaire
Machine or process type
Devices and Machine Builder Library (MBL) objects
Quantities of each object your program will contain. These drive the memory estimate from ARP Studio 5000 v37 MBL benchmarks (includes typical supporting logic).
Local I/O points
Points wired to I/O on the controller rack. ARP adds its I/O spare allowance.
HMI
HMIs connect over EtherNet/IP messaging; ARP does not count them as I/O-tree nodes.
HMI
Communications and networking
Rockwell counts an EtherNet/IP node as a device added directly to the controller’s I/O configuration. Messaging-only connections (HMI, SCADA, OPC UA, MSG, Modbus) are checked separately.
Remote I/O
Motion
Integrated Motion on EtherNet/IP needs a Logix controller. Micro800 offers embedded PTO for basic positioning.
Safety
“Unknown” returns Engineering Review Required.
Safety controller
Application features and performance
Heavy features do not change the memory estimate. They trigger “Performance review required” instead of a guessed CPU load.
Existing standards and generation preference
A customer or plant standard can override the technically smallest CPU.
Controller generation preference
From an existing or similar project. Used instead of benchmarks.
How sizing works
How the Calculator Sizes a PLC
Size a PLC processor by checking every limit the application touches — memory, EtherNet/IP nodes, local I/O, remote I/O, motion axes, safety, communications, and performance — and choosing the smallest controller that passes all of them with spare capacity. I/O count alone does not decide it.
The memory model
Memory is estimated from ARP Studio 5000 v37 Machine Builder Library benchmarks (includes typical supporting logic); verify in Studio 5000 for final selection. If you have a compiled project, enter its memory under Existing standards and that value is used instead. Micro800 program steps are still not estimated.
Memory is not the only rule
- EtherNet/IP nodes: each device added directly to the controller’s I/O configuration counts toward the CPU’s node limit (Rockwell definition). ARP adds a 20% node reserve.
- Local I/O: CompactLogix 5380 supports 8 to 31 local Compact 5000 modules by tier; CompactLogix 5390 supports 16 or 32 PointMax modules. ControlLogix is chassis-based.
- Motion: position-loop drive axes are limited per CPU (for example 8 on a 5034-L9010TS, 32 on a 5034-L9020TS).
- Safety: safety memory and SIL/PL capability differ by family. CompactLogix 5390 reaches SIL 2/PLd; ControlLogix 5590 reaches SIL 3/PLe with a safety partner.
- Performance: fast tasks, heavy messaging, OPC UA, historian traffic, and large data handling return Performance review required. The tool does not invent a CPU-load percentage.
- Architecture and standards: redundancy or 1756 chassis modules require ControlLogix; a customer or plant standard can override the smallest technical fit.
Generation comparison
L9 or Current Generation? How the Calculator Decides
CompactLogix 5380 vs 5390
| Feature | 5390 | 5380 |
|---|---|---|
| Performance (Rockwell) | 2x CompactLogix 5380 | 5–20x CompactLogix 5370 |
| User memory | 400 KB–10 MB | 600 KB–10 MB |
| Axes per controller | 128 max | 32 max |
| EtherNet/IP nodes | 60–300 | 16–180 |
| MSG connections | 384 | 256 |
| Local I/O | PointMax (5034) | Compact 5000 (5069) |
Source: 5034-TD900B-EN-P comparison table.
ControlLogix 5580 vs 5590
| Feature | 5590 | 5580 |
|---|---|---|
| Performance (Rockwell) | 2x ControlLogix 5580 | 5–20x ControlLogix 5570 |
| User memory | 2–80 MB | 3–40 MB |
| Axes per controller | 512 | 256 |
| EtherNet/IP nodes | 30–600 | 100–300 |
| Embedded Ethernet ports | 2 | 1 |
| Logix Designer | v38 and later | v29 and later |
Source: 1756-SG900A-EN-P comparison table.
L9 is recommended when it is justified: you chose L9 for a new design; you asked for the best current architecture with no customer standard; or the application needs a verified L9 capability such as more drive axes, more EtherNet/IP nodes, PointMax I/O, or built-in SIL 2 safety on CompactLogix.
5380 or 5580 is recommended when it fits your standard: an existing 5069 or 1756 installed base, spare-parts standardization, firmware or project compatibility, or no benefit from changing generation. The calculator never treats L9 as automatically better.
CompactLogix-to-ControlLogix transition logic
Move to ControlLogix when CompactLogix cannot meet a requirement — not simply when memory is large. The calculator only selects ControlLogix when every ARP-supported CompactLogix fails a check such as EtherNet/IP nodes, memory, motion, controller redundancy, or a need for 1756 chassis modules, or when your plant standard requires it. The result always states the actual reason and whether memory was the limiting factor.
Published data used
Allen-Bradley Controller Capacity Tables
Every limit below comes from a current Rockwell Automation publication, listed under each table. The calculator reads these same values from one data table, so nothing is hidden in page code.
CompactLogix 5380 (5069)
| Catalog | User memory | Safety memory (Compact GuardLogix) | EtherNet/IP nodes | Local I/O modules | Drive axes (M/P cat.) |
|---|---|---|---|---|---|
| 5069-L306ER | 600 KB | 300 KB | 16 | 8 | 2 |
| 5069-L310ER | 1 MB | 500 KB | 24 | 8 | 4 |
| 5069-L320ER | 2 MB | 1 MB | 40 | 16 | 8 |
| 5069-L330ER | 3 MB | 1.5 MB | 60 | 31 | 16 |
| 5069-L340ER | 4 MB | 2 MB | 90 | 31 | 20 |
| 5069-L350ERM | 5 MB | 2.5 MB | 120 | 31 | 24 |
| 5069-L380ERM | 8 MB | 4 MB | 150 | 31 | 28 |
| 5069-L3100ERM | 10 MB | 5 MB | 180 | 31 | 32 |
Source: Rockwell Automation publication 5069-TD002O-EN-P (November 2023). Node limits apply with Logix Designer v31 or later; 31 local modules with v30 or later. Integrated motion requires an M or P catalog number.
CompactLogix 5390 (5034, L9 generation)
| Catalog | Standard memory | Safety memory | EtherNet/IP nodes | OPC UA nodes | Local PointMax modules | Drive axes |
|---|---|---|---|---|---|---|
| 5034-L9004TS | 400 KB | 400 KB | 60 | 300 | 16 | 8 |
| 5034-L9006TS | 600 KB | 600 KB | 60 | 300 | 16 | 8 |
| 5034-L9010TS | 1 MB | 1 MB | 60 | 300 | 16 | 8 |
| 5034-L9020TS | 2 MB | 2 MB | 200 | 2000 | 32 | 32 |
| 5034-L9030TS | 3 MB | 3 MB | 200 | 2000 | 32 | 32 |
| 5034-L9050TS | 5 MB | 5 MB | 200 | 2000 | 32 | 32 |
| 5034-L9100TS | 10 MB | 10 MB | 300 | 4000 | 32 | 128 |
Source: Rockwell Automation publication 5034-TD900B-EN-P (July 2026). All 5390 controllers are safety-enabled up to SIL 2/PLd and support motion.
ControlLogix 5580 (1756-L8x)
| Catalog | User memory | EtherNet/IP nodes | OPC UA nodes |
|---|---|---|---|
| 1756-L81E | 3 MB | 100 | — |
| 1756-L82E | 5 MB | 175 | 600 |
| 1756-L83E | 10 MB | 250 | 1200 |
| 1756-L84E | 20 MB | 250 | 10000 |
| 1756-L85E | 40 MB | 300 | 15000 |
Source: Rockwell Automation publication 1756-TD001W-EN-P (October 2025). Node limits with Logix Designer v30 or later; OPC UA node limits with v36 or later. Up to 256 axes per controller (1756-SG900A-EN-P). Redundancy supported from Logix Designer v33.00.02.
ControlLogix 5590 (1756-L9, L9 generation)
| Catalog | Standard memory | Safety memory | EtherNet/IP nodes | OPC UA nodes |
|---|---|---|---|---|
| 1756-L902TS | 2 MB | 2 MB | 30 | 300 |
| 1756-L905TS | 5 MB | 5 MB | 100 | 1,000 |
| 1756-L908TS | 8 MB | 8 MB | 200 | 2,000 |
| 1756-L915TS | 15 MB | 12 MB | 300 | 5,000 |
| 1756-L925TS | 25 MB | 12 MB | 400 | 20,000 |
| 1756-L950TS | 50 MB | 12 MB | 500 | 50,000 |
| 1756-L980TS | 80 MB | 12 MB | 600 | 100,000 |
Source: Rockwell Automation publications 1756-TD001W-EN-P (October 2025) and 1756-SG900A-EN-P (September 2025). SIL 2/PLd with one controller; SIL 3/PLe with the 1756-L9SP safety partner. Up to 512 axes. Requires Logix Designer v38 or later.
Micro800
| Controller | Program steps (typical) | Data bytes | Max digital I/O | EtherNet/IP Class 1 nodes | Embedded PTO | Expansion I/O modules |
|---|---|---|---|---|---|---|
| Micro820 (2080-L20E-20…) | 10K | 20 KB | 35 | 4 | — | — |
| Micro850 24-point (2080-L50E-24…) | 10K | 20 KB | 132 | 8 | 2 | 4 |
| Micro850 48-point (2080-L50E-48…) | 10K | 20 KB | 192 | 8 | 3 | 4 |
| Micro870 (2080-L70E-24…) | 20K | 40 KB | 304 | 8 | 2 | 8 |
Source: Rockwell Automation publication 2080-SG001J-EN-P (September 2025). Program steps and data bytes are Rockwell’s “typical” figures; 1 program step = 12 data bytes. Micro800 is programmed in Connected Components Workbench, not Studio 5000.
PLC sizing questions
Allen-Bradley PLC sizing questions, answered directly
Each answer starts with the direct answer, then adds context. Figures come from the Rockwell publications listed in the capacity tables above.
What size CompactLogix PLC do I need?
You need the smallest CompactLogix that holds your compiled program plus a reserve and also meets your EtherNet/IP node, local I/O, motion-axis, and safety needs. CompactLogix 5380 ranges from 0.6 MB (5069-L306ER, 16 nodes) to 10 MB (5069-L3100ERM, 180 nodes); CompactLogix 5390 ranges from 0.4 MB to 10 MB with 60 to 300 nodes. Use the calculator above to check every limit at once.
How much PLC memory do I need?
Enough for your compiled project plus spare. Measure memory from a compiled Studio 5000 project when you can; ARP adds a 30% engineering and future reserve as its default design allowance. Estimates from I/O count alone are unreliable because AOIs, UDTs, alarms, recipes, and messaging all use memory.
Is a 5069-L306ER big enough?
Only for small applications. The 5069-L306ER has 0.6 MB of user memory, supports 16 EtherNet/IP nodes and 8 local I/O modules, and has no integrated motion unless you choose the 5069-L306ERM (2 drive axes). If your compiled program with reserve exceeds 0.6 MB or you need more than 16 nodes, step up.
5069-L310ER vs 5069-L320ER?
The 5069-L320ER doubles memory from 1 MB to 2 MB, raises EtherNet/IP nodes from 24 to 40, and raises local I/O modules from 8 to 16. With motion, the L320ERM supports 8 drive axes versus 4 on the L310ERM. Choose the L320ER when the L310ER fails any of those limits after reserve.
5069-L320ER vs 5069-L330ER?
The 5069-L330ER adds 1 MB of memory (3 MB vs 2 MB), raises EtherNet/IP nodes from 40 to 60, and raises local I/O modules from 16 to 31. With motion, the L330ERM supports 16 drive axes versus 8. Nodes or local modules often decide this step before memory does.
CompactLogix 5380 vs CompactLogix 5390?
CompactLogix 5390 is the newer L9 generation: Rockwell rates it at 2x the performance of 5380, with up to 128 axes (vs 32), 60 to 300 EtherNet/IP nodes (vs 16 to 180), and SIL 2/PLd safety built into every controller. CompactLogix 5380 remains the right fit for an existing 5069 standard. The 5390 uses PointMax local I/O instead of Compact 5000 I/O.
What is CompactLogix 5390?
CompactLogix 5390 is Rockwell Automation’s L9-generation CompactLogix controller family (catalog 5034-L9xxxTS). It offers 400 KB to 10 MB of standard memory with equal safety memory, 60 to 300 EtherNet/IP nodes, up to 32 local PointMax I/O modules, and integrated motion and SIL 2/PLd safety on every model.
What is the Allen-Bradley L9 processor family?
L9 is Rockwell Automation’s newest Logix controller generation: CompactLogix 5390 (5034-L9xxxTS) and ControlLogix 5590 (1756-L9xxTS). Rockwell rates each at 2x the performance of the 5380 and 5580 controllers they follow, and each “TS” model includes safety capability. L9 requires Studio 5000 Logix Designer v38 or later for ControlLogix 5590.
What size ControlLogix processor do I need?
Choose the smallest ControlLogix whose memory, EtherNet/IP node limit, and safety memory cover your design with reserve. ControlLogix 5580 runs from 3 MB (1756-L81E, 100 nodes) to 40 MB (1756-L85E, 300 nodes); ControlLogix 5590 runs from 2 MB (1756-L902TS, 30 nodes) to 80 MB (1756-L980TS, 600 nodes).
ControlLogix 5580 vs ControlLogix 5590?
ControlLogix 5590 is the L9 generation: Rockwell rates it at 2x 5580 performance, with up to 512 axes (vs 256), 30 to 600 EtherNet/IP nodes (vs 100 to 300), two embedded Ethernet ports, and built-in safety memory. ControlLogix 5580 needs Logix Designer v29 or later; 5590 needs v38 or later. A plant standardized on 1756-L8x may still be best served by 5580.
1756-L81E vs L82E?
The 1756-L82E has 5 MB of memory versus 3 MB on the 1756-L81E, and supports 175 EtherNet/IP nodes versus 100 (Logix Designer v30 or later). Rockwell also lists 600 OPC UA nodes for the L82E, and no OPC UA node figure for the L81E.
How much PLC memory does a VFD use?
ARP’s Studio 5000 v37 benchmark for a Motor_VSD object with a PowerFlex 525 drive profile is about 2,362 memory blocks (~2.3 KB), including typical supporting logic. The calculator uses that figure for each VFD object and still adds ARP’s 30% design reserve. Verify the final selection in Studio 5000.
How much memory does a Machine Builder Library object use?
It varies by object type. ARP’s current estimates come from Studio 5000 v37 measurements on a 5069-L310ERS2: about 338 blocks for a Motor_Contactor, about 2,362 for a Motor_VSD with PowerFlex 525, with analog at 75% of the contactor figure and complex objects (Equipment Module, Unit, axis handler, and similar) at the VFD-scale default. Values include typical supporting logic; verify in Studio 5000 for final selection.
How many motors can a CompactLogix control?
There is no fixed motor count. Hardwired motors are limited by local I/O modules (8 to 31 on CompactLogix 5380) and program memory; networked drives are limited by the EtherNet/IP node limit (16 to 180 on 5380, 60 to 300 on 5390). Count your devices in the calculator to see which limit applies first.
How many PowerFlex drives can a CompactLogix control?
Each PowerFlex drive added to the I/O configuration uses one EtherNet/IP node, so the node limit sets the ceiling: 16 to 180 on CompactLogix 5380 and 60 to 300 on CompactLogix 5390, minus every other networked device. ARP keeps a 20% node reserve.
How many EtherNet/IP devices can a CompactLogix handle?
CompactLogix 5380 supports 16 to 180 EtherNet/IP nodes and CompactLogix 5390 supports 60 to 300, depending on the CPU. Rockwell counts a node as a device added directly to the controller’s I/O configuration; HMIs and messaging peers use connections instead.
How much spare PLC memory should I leave?
Leave what your specification requires; ARP’s default design allowance is 30% above the measured project memory for future changes and online edits. Rockwell does not publish a required spare percentage, so treat this as a design choice and confirm it with your customer standard.
When should I move from CompactLogix to ControlLogix?
Move to ControlLogix when CompactLogix cannot meet a requirement, not simply when the program is large. Typical triggers are more than 300 EtherNet/IP nodes (the CompactLogix 5390 maximum), more than 10 MB of memory, controller redundancy, 1756 chassis modules, or a plant standard. The calculator states the actual reason and whether memory was the limiting factor.
Is CompactLogix large enough for my machine?
Usually, if your program fits 10 MB with reserve and you need no more than 180 (5380) or 300 (5390) EtherNet/IP nodes, no controller redundancy, and no 1756 chassis modules. Motion and safety limits also apply per CPU. The calculator shows exactly which limit, if any, pushes you to ControlLogix.
Micro850 vs CompactLogix?
Micro850 suits small standalone machines: 10K typical program steps, up to 192 digital I/O, and 8 EtherNet/IP Class 1 nodes, programmed in Connected Components Workbench. Choose CompactLogix when you need Studio 5000, more networked devices, integrated servo motion, a safety controller, or remote I/O. See the PLC family selector for a family-level comparison.
How do I size a PLC processor?
Check every limit the application touches — program memory, EtherNet/IP nodes, local I/O, remote I/O, motion axes, safety, communications, and performance — then pick the smallest controller that passes all of them with a design reserve. Measure memory from a compiled project whenever possible.
Does PLC I/O count determine processor size?
No. I/O count affects local module limits, but processor size is usually set by program memory, networked device count, motion axes, safety, or performance. Two machines with the same I/O can need different CPUs.
Does an HMI use PLC memory?
Indirectly. The HMI itself runs in the terminal, but HMI faceplate tags, alarm structures, and the interface logic in the controller use controller memory, and each HMI uses messaging connections. ARP counts HMIs against connections, not EtherNet/IP I/O nodes.
Do AOIs use PLC memory?
Yes. Each Add-On Instruction definition uses memory once, and each instance adds its own tag data. That is why ARP benchmarks library objects for both one-time overhead and per-instance memory.
Does motion require a larger PLC?
Often. Each CPU has a maximum number of position-loop drive axes — for example 4 on a 5069-L310ERM, 8 on a 5034-L9010TS, and 32 on a 5034-L9020TS — and motion adds program and task load. A CPU with enough memory can still be too small for the axis count.
Does GuardLogix need separate safety memory?
Yes. Safety programs run in dedicated safety memory with its own limit. Compact GuardLogix 5380 safety memory is half of user memory (0.3 MB to 5 MB); CompactLogix 5390 safety memory equals standard memory; ControlLogix 5590 safety memory runs from 2 MB up to 12 MB.
Next step
Build This Control Panel
Run the calculator, then use Build This Control Panel to carry your answers into the ARP RFQ Builder so you don’t have to enter them twice. You can also take the result to the enclosure size calculator or the cost guide.
Have drawings, a BOM, an I/O list, or an existing Studio 5000 project report? Send them with your request on our Contact page.
Call 314-916-1097 — we’ll respond within 30 minutes.
Automation Ready Panels specializes in configurable Allen-Bradley control panels. Qualifying standard configurations are quoted, designed, programmed, and shipped in 7–10 business days. Larger, safety, motion, redundant, or nonstandard builds, and component availability, need schedule review.